Trane Roof Top Unit Model Number Descriptions

NOTE: This information has not been certified by the manufacturer. ENSURE that you verify all of this model number information with the manufacturer before using this information to make equipment selection or repair decisions.

Trane RTU Model Number Descriptions 3 to 10 tons (T/Y – 17 SEER Plus)

 

Digit 1 – Unit Type

T     DX Cooling

Y     DX Cooling, Gas Heat

 

Digit 2 – Efficiency

S     Standard Efficiency

H     High Efficiency

 

Digit 3 – Airflow

C     Convertible

 

Digit 4, 5, 6 – Nominal Gross Cooling Capacity (MBh)

037     3 Ton (17 SEER)

047     4 Ton (17 SEER)

067     5 Ton (17 SEER)

 

Digit 7 – Major Design Sequence

E     R-410 Refrigerant

 

Digit 8 – Voltage Selection

3     208-230/60/3

4     460/60/3

W     575/60/3

 

Digit 9 – Unit Controls

R     ReliaTel Microprocessor

 

Digit 10 – Heating Capacity

Note: The below are applicable to Digit 1, T models only

0     No Electric Heat

B    6kW (3 phase)

E     12kW (3 phase)

G     18kW (1&3 phase)

J     23kW (3 phase)

Note: The below are applicable to Digit 1, Y models only

L     Low Heat

M     Medium Heat

H     High Heat

X   Low Heat, Stainless Steel Heat Exchanger

Y   Medium Heat, Stainless Steel Heat Exchanger

Z   High Heat, Stainless Steel Heat Exchanger

 

Digit 11 – Minor Design Sequence

A     First Sequence [16]

 

Digit 12, 13 – Service Sequence

**     Factory Assigned

 

Digit 14 – Fresh Air Selection

0     No Fresh Air

A     Manual Outside Air Damper 0-50% [2]

B     Motorized Outside Air Damper 0-50%

C     Economizer, Dry Bulb 0-100% without Barometric Relief [5]

D     Economizer, Dry Bulb 0-100% with Barometric Relief [5]

E     Economizer, Reference Enthalpy 0-100% without Barometric Relief [5]

F     Economizer, Reference Enthalpy 0-100% with Barometric Relief [5]

G     Economizer, Comparative Enthalpy 0-100% without Barometric Relief [5]

H     Economizer, Comparative Enthalpy 0-100% with Barometric Relief [5]

K     Low Leak Economizer with Barometric Relief

M     Low Leak Economizer with Reference Enthalpy with Barometric Relief

P     Low Leak Economizer with Comparative Enthalpy with Barometric Relief

 

Digit 15 – Supply Fan/Drive Type/Motor

0     Standard Drive [4]

6     Single Zone VAV [34]

E   VAV Supply Air Temperature Control Standard Motor [34]

 

Digit 16 – Hinged Service Access/Filters

0     Standard Panels/Standard Filters

A   Hinged Access Panels/Standard Filters

B   Standard Panels/2” Merv 8 Filters

C   Hinged Access Panels/2” Merv 8 Filters

D   Standard Panels/2” Merv 13 Filters

E   Hinged Access Panels/2” Merv 13 Filters

 

Digit 17 – Condenser Coil Protection

0     Standard Coil

1     Standard Coil with Hail Guard

2     Black Epoxy pre-Coated Condenser Coil

3     Black Epoxy pre-Coated Condenser Coil with Hail Guard

4     CompleteCoat Condenser Coil

5     CompleteCoat Condenser Coil with Hail Guard

 

Digit 18 – Through-the-Base Provisions

0     No Through-the-Base Provisions

A     Through-the-Base Electric [6]

B     Through-the-Base Gas Piping [13]

C   Through-the-Base Electric and Gas Piping [13]

 

Digit 19 – Disconnect/Circuit Breaker (three-phase only)

0     No Disconnect/No Circuit Breaker

1     Unit Mounted Non-Fused Disconnect [6]

2     Unit Mounted Circuit Breaker [6]

 

Digit 20 – Convenience Outlet

0     No Convenience Outlet

A     Unpowered Convenience Outlet

B     Powered Convenience Outlet (three-phase only) [7]

 

Digit 21 – Communication Options

0     No Communications Interface

2     LonTalk Communications Interface

3     Novar 2024 Controls

4     Novar 3051 Controls Without Zone Sensor

5     Novar 3051 Controls Interface with DCV

6     BACnet Communications Interface

7     Air-Fi Wireless Communications [22]

 

Digit 22 – Refrigeration System Options

0     Standard Refrigeration System8

B     Dehumidification Option [17]

 

Digit 23 – Refrigeration Controls

Note: The below are applicable to Digit 7 = E

0     No Refrigeration Control [3]

1     Frostat

2     Crankcase Heater [1]

3     Frostat  and Crankcase Heater [1]

 

Digit 24 – Smoke Detector [14]

0     No Smoke Detector

A     Return Air Smoke Detector [9, 10]

B     Supply Air Smoke Detector

C     Supply and Return Air Smoke Detectors

D     Plenum Smoke Detector

 

Digit 25 – System Monitoring Controls

0     No Monitoring Control [11]

1     Clogged Filter Switch [11]

2     Fan Failure Switch [11]

3     Discharge Air Sensing Tube [11]

4     Clogged Filter Switch and Fan Failure Switch [11]

5     Clogged Filter Switch and Discharge Air Sensing Tube [11]

6     Fan Failure Switch and Discharge Air Sensing Tube [11]

7     Clogged Filter Switch, Fan Failure Switch and Discharge Air Sensing Tube [11]

8     Novar Return Air Sensor (NOVAR 2024) [12, 20]

9     Novar Zone Temp Sensor (NOVAR 3051) [15, 20]

A     Condensate Drain Pan Overflow Switch

B     Clogged Filter Switch [11] and Condensate Drain Pan Overflow Switch

C     Fan Failure Switch [11] and Condensate Drain Pan Overflow Switch

D     Discharge Air Sensing [11] and Condensate Drain Pan Overflow Switch

E     Clogged Filter Switch [11], Fan Failure Switch [11] and Condensate Drain Pan Overflow Switch

F     Clogged Filter Switch [11], Discharge Air Sensing Tube [11] and Condensate Drain Pan Overflow Switch

G     Fan Failure Switch [11] Discharge Air Sensing Tube [11] and Condensate Drain Pan Overflow Switch

H     Clogged Filter Switch [11], Fan Failure Switch [11] Discharge Air Sensing [11] and Condensate Drain Pan Overflow Switch

 

Digit 26 – System Monitoring Controls

0     No Monitoring Controls

A     Demand Control Ventilation (CO2) [18, 19]

B     Low Leak Economizer with FDD (Fault Detection & Diagnostics)

C     FDD (Fault Detection & Diagnostics) with DCV (Demand Control Ventilation)

 

Digit 27 – Unit Hardware Enhancements

0     No Enhancements

1     Stainless Steel Drain Pan

 

Digit 31 – Advanced Unit Controls

0     Standard Unit Controls

1     Human Interface

 

Model Number Notes

1     Standard on all variable stage units.

2     Manual outside air damper will ship factory supplied within the unit, but must be field installed.

3     High pressure control is standard on all units.

4     Direct drive is standard for 3 to 5 ton variable stage units.

Digit 15 = 0, 6

3 Phase (3 to 5 Ton) – High Efficiency Constant CFM

5     Economizer with Barometric Relief is for downflow configured units only. Order economizer without Barometric Relief for horizontal configuration. Barometric Relief for horizontal configured units must be ordered as field installed accessory.

6     Through-the-base electric required when ordering disconnect/circuit breaker options.

7     Requires use of disconnect or circuit breaker.

Not Available

High Efficiency

3 to 5 Tons w/Standard Indoor Motor w/460V or 575V

8     Standard metering devices are TXVs.

9      The return air smoke detector may not fit up or work properly on the Precedent units when used in conjunction with 3rd party accessories such as bolt on heat wheels, economizers and power exhaust. Do not order the return air smoke detectors when using this type of accessory.

10   Return Air Smoke Detector cannot be ordered with Novar controls.

11   These options are standard when ordering Novar controls.

12   This option is used when ordering Novar controls.

13   Includes gas piping and shutoff (field assembly required).

14   Not available with high temperature duct sensor accessory.

15   Novar sensor utilized with Digit 21 = (4) Novar 3051 controls without zone sensor.

16   Available for T/Y 3, 4, 5 ton high efficiency models.

17   Requires selection of 2” pleated filters (option B or C) for Digit 16.

18   Not available on all single phase or standard efficiency.

19   Demand Control Ventilation Option includes wiring only. The CO2 sensor is a field-installed only option.

20   Novar is not available with SZVAV products.